Item |
Specifications |
Measuring input |
Number of inputs: 2 points/module, 4 points/module
Input type: Thermocouple, RTD, DC current, DC voltage *Universal input (Z-TIO) |
Control method |
PID control with autotuning, ON/OFF control (Z-TIO) |
Control output |
Relay contact output, Voltage pulse output 0/12V DC, Continuous DC voltage output
DC current output, Triac output, Open collector output (Z-TIO) |
Alarm |
Temperature alarm, Heater break alarm, Control loop break alarm (Z-TIO) |
Digital input |
Number of input: 8 points/module
Input method: Voltage contact input (Open: Less than 5V DC, Close: More than 17.5V DC)
Function: Run/Stop, Remote/Local, Auto/Manual, Memory area selection, Alarm interlock reset (Z-DIO) |
Digital output |
Number of output: 8 points/module
Output method: Relay contact output, Open collector output
Function: Alarm output (Temperature alarm, Heater break alarm, Control loop break alarm) (Z-DIO) |
Host communication |
Communication method: RS-485, RS-422A
Communication protocol: ANSI X3.28-1976 sub-category 2.5B4 (RKC standard) |
Power supply |
24V DC |
|
|
|